South Korean data center ran 12-yr-old batteries 60cm from servers — 647 systems down
In September 2025 a lithium battery exploded during a safety exercise at South Korea's NIRS data center, knocking out 647 government systems for weeks.
National Information Resources Service (NIRS) · LG Energy Solution · 2025-09-26
What happened
On 26 September 2025 a lithium-ion battery exploded during a routine risk-reduction exercise to relocate UPS units at South Korea's NIRS data center in Daejeon, the backbone of government digital services. The batteries, made by LG Energy Solution and installed in 2012-13, had already exceeded their rated 10-year lifespan, and the UPS racks sat about 60cm from the server racks they protected. Firefighters fought the blaze for roughly 22 hours, using CO2 suppression rather than water to avoid spreading the chemical fire.
The blast destroyed 384 batteries and knocked out 647 government systems — 96 destroyed outright and 551 shut down pre-emptively. Some agencies lost data that could not be recovered, and the National Cyber Security Center raised the cyber threat level from Attention to Caution. The fire echoed the 2022 KakaoTalk outage and forced President Lee Jae-myung to call the disaster 'foreseeable', as the facility had no real twin-server failover despite being the government's redundancy hub.
The failure was a design decision, not an act of God: batteries kept in service past their rated life, installed dangerously close to the servers they were meant to protect, and a backup system that could not actually take over. The Critical Information Infrastructure handled by NIRS — immigration, land registration, customs — went dark for weeks, with one official noting the recovery could span a month.
Why it happened
- LG Energy Solution lithium batteries installed in 2012-13 were still in service past their roughly 10-year rated lifespan, and a known failure mode turned a relocation exercise into an explosion.
- UPS racks sat only about 60cm from server racks, so a single battery fire could reach the very systems it was supposed to keep alive.
- Despite being the government's redundancy hub, NIRS had no real-time twin-server failover, so when the primary failed there was nothing to catch it.
- The cost-saving layout traded physical separation and failover for density, and the safety exercise itself became the trigger.
The lesson
A backup works only if it is designed to actually take over. A UPS a foot from the server, past its rated life, with no twin to fail over to, is a single point of failure wearing a backup's uniform.
Aftermath
South Korea's cyber threat level was raised and the National Cyber Security Center issued a caution. LG Energy Solution and the government faced scrutiny over battery age and placement, and the facility's lack of real-time failover became the central lesson for state data centers. Agencies dependent on NIRS — immigration, land, customs — spent weeks on partial recovery, with some data losses confirmed irretrievable.
Sources
- Network World — South Korea's data center fire triggers global scrutiny of lithium-ion batteries and DR architecture
- The Chosun Daily — Fire at NIRS Daejeon data center halts 647 government systems
- CNN — South Korea data center fire 'paralyzes' vital services
spotted an error? The club wants to know.
More like this
Coupang's 2025 breach: 34M accounts exposed by a former employee's data key
Colonial Pipeline paid $4.4M in ransom — because it couldn't find the backup
Korea's homegrown WiBro network shut down after 12 years — LTE won the standard war
Somewhere, someone solved the problem this company failed at. 2nd Opinion →

Comments · 0
Sign in to join the comments.